True RMS digital metering with single cycle capture
Multi-function timing system
Large back-lit liquid crystal display
Thermal and over-current protection
Automatic switch-off at end of test
Compact and portable
Automatic mains voltage selection*
Clear and simple user interface
Optional ADMlog PC data capture software
*See specifications
750ADM mk2 data sheet v0
523.45kb
ADMlog v1 Data sheet rev 1
277.09kb
The 750ADM mk2and 750ADM-H mk2are compact, rugged primary current injection systems with a 750A output capability. The 750ADM has a maximum no load output voltage of 3.5V and the 750ADM-H has a maximum voltage of 5V. The units are ideally suited to all low power primary injection tasks requiring up to 750A for short periods.
Where higher currents and powers are required for primary injection, 7kVA and 20kVA primary injection systems are available. The PCU1-SP and PCU2/E systems have separate control and loading units, allowing a wide range of load conditions to be covered with different loading units.
Unit type
Max. power rating
Max. current
750ADM
2kVA
750A 30s*
750ADM-H
3kVA
750A 20s*
PCU1-SP+NLU5000
11.5kVA
5000A 40s
PCU2/E+LU6000
20kVA
6000A 5 min
*10s on 115V supply
The750ADM and 750ADM-Hhave two outputs, allowing injection of currents as low as a few hundred milliamps and up to 750A. Voltages up to 16V are available on the 40A output, allowing higher impedance trips to be tested. Four true RMS metering ranges are provided, allowing the full scale of the meter and trip level to be set independently of the selected output. The metering has a capture time of less than 20ms, allowing the RMS of a single cycle to be accurately measured. Industry standard connectors are used on all inputs and outputs for convenience, reliability and safety.
The 750ADM and 750ADM-H are comprehensively protected by electronic overcurrent and thermal trips.
The timing system is very flexible without compromising ease of use, allowing trip times, reset times and reclose times to be quickly measured to a high degree of accuracy. Two contact inputs are provided, each of which may be trigged by a volt-free contact or a dc voltage. The contact inputs auto-sense for normally open or normally closed contacts.
The 750ADM can be used to test many devices including:
Circuit breakers
Primary injection of over-current relays
Auto-reclosers
MCB’s
CT ratio (with external meter for secondary current)
The 750ADM-ALrange of high current leads are available to complement the 750ADM.Click here for details.