Greatly improves timing accuracy when testing
electromechanical relays
Wide range of test currents
High overload capability
50/60Hz operating frequency
High efficiency
Current monitoring output
Compact and portable
100ADM-F RB10 Data sheet rev 1
337.11kb
The 100ADM-F filter unit reduces the level of current harmonics when testing electro-mechanical protection relays. It is designed for use with our range of secondary injection test sets.
All electromechanical protection relays have iron cores that saturate and distort the test current under high overload test conditions. This distortion causes significant errors in the measured trip time of these relays during testing. Distortion of the waveform can be a particular problem with disc induction type over-current and sensitive earth fault relays.
For example, testing a CDG11 disc induction over-current relay without a filter causes significant timing errors. The results below show the errors for a 1.3s 1A CDG11 over-current relay on its 0.5A plug setting, tested at 5A.
Current
THD
Trip time
Error
No Filter
5A
34.5%
1.54s
18.5%
With Filter
5A
6.12%
1.30s
0%
The effect of the filtering on the current may be clearly seen in the waveforms below.
The 100ADM-F has nine current ranges covering 0.25A to 100A and is supplied in an insulated case complete with protective cover and carrying strap.