PCU1-SP Primary Current Injection System


PCU1-SP and NLU5000

Features (PCU1-LT and PCU1-SP)

  • 5kA maximum output current
    (higher overload currents for 2s)
  • Multi-function digital timing system
  • Digital true RMS memory ammeter
  • Solid state switching
  • 2000A and 5000A loading units
  • Three range outputs on loading units
  • Rugged, compact design
  • Optional trolley mounting of system

PCU1-SP Additional Features

  • Secondary injection up to 100A
  • Auxiliary metering input
  • Direct reading CT ratio and polarity


PCU1-SP system mounted on trolley


PCU1-LT-SP Data sheet rev 4

284kb

ADMlog v1 Data sheet rev 1

277.09kb

The PCU1 series are medium powered primary current injection systems offering output currents up to 5000A. The system consists of a separate control unit containing all metering and control functions and a loading unit that provides the high current output. The PCU1-LT and PCU1-SP are ideally suited to primary current injection, stability testing and circuit breaker testing. In addition, the SP version offers direct-reading CT ratio and polarity tests and a 100A secondary injection output. T&R also offer the higher-powered PCU2/E system.

Feature

PCU1-LT

PCU1-SP

PCU2/E

Primary injection

Yes

Yes

Yes

Maximum output power

11.5kVA
40s

11.5kVA
40s

20kVA
5 min

Secondary current injection

No

100A

No

CT ratio/polarity test

No

Yes

No

Two loading units are available, delivering a maximum output current of 2000A or 5000A. Each loading unit has three output taps to allow for a wide range of load impedances. For example, the NLU5000 may be configured to either give a maximum current of 5000A on the 2.3V range, 2500A on the 4.6V range or 1250A on the 9.2V range.

The control units are rated at 11.5kVA with a 2 second overload capability of 23kVA using pulse mode. All metering is digital and a memory facility is provided to hold the current reading when the output trips or is switched off. The current isswitched by a solid state deviceand is automatically switched off when the device under test trips.

The PCU1 systems have a high accuracy timing system, allowing timing tests to be carried out to a resolution of 1ms. Selection for normally open or normally closed contacts is automatic, and the status of the contacts is shown on the front panel. Timing modes are available to test under and over current devices, re-closers, under and over voltage devices, current trips and circuit breakers.

A full range of high current output leads are available to complement the system in a range of lengths.









 
PCU1-SP Specification 


  Other Pages
  • Current Injection
  • 200ADM Current Injection System
  • 100ADM mk4 Current Injection System
  • 100ADM-F Current Filter Unit
  • 100A/E Current Injection system
  • CIT Primary Current Injection System
  • PCU1 Primary Current Injection System
  • PCU2 Primary Current Injection System
  • 50A-3PH Three Phase Current Injection System
  • 200A-3PH/ED Three Phase Current Injection System
  • 750ADM mk2 Current Injection System
  • 750ADM-AL Lead Set
  • 200ADM-P Current Injection System
  • 200ADM-P Specification
  • 100/200ADM-AL Lead set
  • RB10 Resistor Box


    Sub Categories

    right margin
    bottom margin
       
    T&R Test Equipment | Tel. +44 (0)1483 207428
    info@trtest.com | Top | Site map