100ADM-F

ISO View 1 03-10-12 with Grey FPFeatures

  • Forces test current to a sinusoid
  • Greatly improves timing accuracy when testing
    electromechanical relays
  • Wide range of test currents
  • High overload capability
  • 50/60Hz operating frequency
  • High efficiency
  • Current monitoring output
  • Compact and portable

 

Product Data

The 100ADM-F filter unit reduces the level of current harmonics when testing electro-mechanical protection relays. It is designed for use with our range of secondary injection test sets.

All electromechanical protection relays have iron cores that saturate and distort the test current under high overload test conditions. This distortion causes significant errors in the measured trip time of these relays during testing. Distortion of the waveform can be a particular problem with disc induction type over-current and sensitive earth fault relays.

For example, testing a CDG11 disc induction over-current relay without a filter causes significant timing errors. The results below show the errors for a 1.3s 1A CDG11 over-current relay on its 0.5A plug setting, tested at 5A.

Current

THD

Trip time

Error

No Filter

5A

34.5%

1.54s

18.5%

With Filter

5A

6.12%

1.30s

0%

The effect of the filtering on the current may be clearly seen in the waveforms below.

1062486830

The 100ADM-F has nine current ranges covering 0.25A to 100A and is supplied in an insulated case complete with protective cover and carrying strap.

Current Ranges and Ratings

The 100ADM-F has the following ranges:

Range Continuous rating 5 min on/ 15 min off
0.25A 0.125A 0.25A
0.5A 0.25A 0.5A
1A 0.5A 1A
2.5A 1.25A 2.5A
5A 2.5A 5A
10A 5A 10A
25A 12.5A 25A
50A 25A 50A
100A 50A 100A

Frequency

The unit may be used at either 50Hz or 60Hz, selectable by a switch on the front panel.

Range Selection

The lower ranges (0.25A-50A) are selected by a switch, and the highest current range is selected by a terminal.

Current Monitor

A current monitoring output is provided on all the filter units that provides an output of 0-100mA corresponding to the rated current for the range.

Filter Unit Impedance

The table below give the impedance in ohms of the filter unit against frequency on each range.

Range Impedance (Ω)
50Hz 150Hz 250Hz 350Hz
0.25A 880Ω 17.5kΩ 30.4kΩ 41.5kΩ
0.5A 220Ω 4.38kΩ 7.65kΩ 10.3kΩ
1A 47.7Ω 950Ω 1.65kΩ 2.25kΩ
2.5A 7.8Ω 150Ω 250Ω 360Ω
5A 1.94Ω 38Ω 65Ω 90Ω
10A 510mΩ 9.5Ω 16.5Ω 22.5Ω
25A 85mΩ 1.5Ω 2.5Ω 3.6Ω
50A 22mΩ 380mΩ 650mΩ 900mΩ
100A 5.5mΩ 95mΩ 165mΩ 225mΩ

Temperature Range

Storage -20°C to 60°C
Operating 0°C to 45°C
Unit Dimensions Weight
100ADM-F 340mm x 230mm x 330mm 15.6kg

Accessories Supplied:

Operating manual
Current monitor plug and lead

Optional Accessories:

Delta-Star Supply Transformer

Delta-Star Supply Transformer

The optional delta-star supply transformer allows operation from 115V, 230V, 400V, and 440V 3 wire supplies, selected by a switch on the unit. An auxiliary single phase output is also provided to supply power to a DVS3 mk2 voltage source.   ...
ES30, ES50, ES100

ES30, ES50, ES100

Features For earthing high voltage connections Highly flexible, clear silicone covered earth cable      
NAL2000/NAL5000

NAL2000/NAL5000

Features High current output leadset for PCU1-SP              
100/200ADM-AL Lead Set

100/200ADM-AL Lead Set

100/200ADM-AL 5m leads Standard 100/200ADM-AL Lead Set specifications The 100ADM and 200ADM-P are supplied with a 5m lead set consisting of: 2x5m long25mm2 100A leads terminated in M10 fork crimps 2x5m, 2x0.5m long 2.5mm2 25A leads terminated...